TIMM’S OVERFILL PREVENTION CONTROLLER EUS-2
Optimum safety for bottom loading tank trucks
The bottom loading of road tank trucks at oil terminals and refineries is characterised by the simultaneous loading of fluids into closed tanker
compartments with high loading rates and no manual supervision.
To prevent hazardous spills, the accumulation of electrostatic charges and the evaporation of emissions, an emergency shut-off system,
supervised grounding and vapour collection is mandatory by law to ensure safe loading processes.
Functional Principle:
The Overfill Prevention Controller EUS-2 is the central component of the overfill prevention system according to European VOC Directive 94/63/EC and American API RP 1004.
EUS-2 monitors the level sensors at the tanker compartments, the truck grounding and the vapour recovery connection. If a critical situation is
detected, the filling process is interrupted immediately at the loading gantry. The controller is able to detect the type of truck installation
and automatically activates the required operating mode.
Application Areas:
The EUS-2 controller is installed at the loading gantry and connected via its control outputs to the control system or loading computer.
It is compatible with all trucks with optical or NTC thermistor high level sensors compliant with EN 13922 (five-wire and two-wire).
The sensors are mounted firmly to the truck’s tank compartments and wired to a standard connecting socket. Products to load are for instance gasoline,
diesel, jet fuel or ethanol (gas group IIB).
Benefits:
- Continuous self-testing of all safety-related functions
- Plain text display for messages in operator’s home language
- Self-explanatory configuration via joystick navigation
- Supports up to 8 two-wire and 12 five-wire sensors
- Clearly visible LEDs
- Two self-monitored control outputs, configurable outputs and a serial data interface
- ‘Parking position’ signal for the truck plug
- Highest safety levels in in hazardous areas
- Leading technology in monitoring, diagnostics and configuration
- Easy to operate through ability to open housing in hazardous areas
Technical Specifications:
-
Type of protection according to ATEX 2014/34/EU:
II 2 [1] G – Ex eb ib q [ia Ga] IIB T4 Gb
-
Power supply:
230 V AC ± 10 %, 50 - 60 Hz, approx. 25 VA
-
Control outputs:
2 potential-free closing contacts
2 change-over contacts | 2 NAMUR-outputs
-
Operating temperature: - 40°C up to + 60°C
-
Approvals: ATEX, IECEx, EAC Ex, PESO
-
Tank Storage Award 2017: Most invaluable product
ACCESSORIES
COILED CABLES WITH PLUGS
For direct connection extendable up to 7.5m
With disconnector plug extendable up to 7.5m
10-pole plug | 4 locking pins according to EN 13922 and 2-wire
7-pole plug | 3 locking pins according to API RP 1004
JUNCTION BOXES
For direct connection of two coiled cables
With disconnector socket for one coiled cable
With disconnector socket and ‘parking socket’ recommended
With two disconnector sockets without ‘parking sockets’ available
Disconnector socket for installation on vapour recovery arm